Tuesday, 10 February 2015

Kunlun Fuel Tank Monitoring System Installation:

Kunlun Fuel Tank Monitoring System Installation:

Fetch the flange at the tank’s fuel hatches.

Insert the probe into the installation orifice of the installation flange.

Install the Ajustable fitting,O-ring seal,Flange,Product Float, Interface Float and the Nylon Stopper on the probe in turn, then lock the Snap Ring.

Insert the probe into the fuel hatches.

Raise the probe after it is put at the bottom of the tank, make sure that the distance between the end of the probe and the bottom of the tank is 2~10mm,prevent the probe from getting curving and screw down the probelocknut.

Install the installation flange closely.















Video:
tank gauging system automatic tank gauge fuel tank monitoring system